I2t Motor overload protection Description Note: For stepper motors, only the rated current is specified, not a maximum current. No liability is therefore assumed when using I2t with stepper motors. The goal of I2t motor overload protection is to protect the motor from damage and, at the same time, operate it normally up to its thermal limit. Object entries The following objects affect I2t motor overload protection: 6075h Motor Rated Current – specifies the rated current in mA. 6073h Max Current – specifies the maximum current in tenths of a percent of the set rated current. 3219h:01hI²t Duration Of Max Current - specifies the maximum duration of the maximum current in ms. Activation Closed loop must be activated. To activate the mode, you must describe the three object entries mentioned above in a meaningful way. This means that the maximum current must be greater than the rated current and a time value for the maximum duration of the maximum current must be entered. If these conditions are not met, the I2t functionality remains deactivated. Function of I2t From the specification of rated current, maximum current and maximum duration of the maximum current, an I2tLim is calculated. The motor can run with maximum current until the calculated I2tLim is reached. The current is then immediately reduced to the rated current. The maximum current is limited by the maximum motor current (6073h). The relationships are illustrated again in the following diagrams. In the first section, t1, the current value is higher than the rated current. At time t1Lim, I2tLim is reached and the current is limited to the rated current. A current that corresponds to the maximum current then occurs for a period of time t2. Hence, the value for I2tLim is reached more quickly than in time t1.
I2t Motor overload protection Description Note: For stepper motors, only the rated current is specified, not a maximum current. No liability is therefore assumed when using I2t with stepper motors. The goal of I2t motor overload protection is to protect the motor from damage and, at the same time, operate it normally up to its thermal limit. Object entries The following objects affect I2t motor overload protection: 6075h Motor Rated Current – specifies the rated current in mA. 6073h Max Current – specifies the maximum current in tenths of a percent of the set rated current. 3219h:01hI²t Duration Of Max Current - specifies the maximum duration of the maximum current in ms. Activation Closed loop must be activated. To activate the mode, you must describe the three object entries mentioned above in a meaningful way. This means that the maximum current must be greater than the rated current and a time value for the maximum duration of the maximum current must be entered. If these conditions are not met, the I2t functionality remains deactivated. Function of I2t From the specification of rated current, maximum current and maximum duration of the maximum current, an I2tLim is calculated. The motor can run with maximum current until the calculated I2tLim is reached. The current is then immediately reduced to the rated current. The maximum current is limited by the maximum motor current (6073h). The relationships are illustrated again in the following diagrams. In the first section, t1, the current value is higher than the rated current. At time t1Lim, I2tLim is reached and the current is limited to the rated current. A current that corresponds to the maximum current then occurs for a period of time t2. Hence, the value for I2tLim is reached more quickly than in time t1.
Description Note: For stepper motors, only the rated current is specified, not a maximum current. No liability is therefore assumed when using I2t with stepper motors. The goal of I2t motor overload protection is to protect the motor from damage and, at the same time, operate it normally up to its thermal limit.
Object entries The following objects affect I2t motor overload protection: 6075h Motor Rated Current – specifies the rated current in mA. 6073h Max Current – specifies the maximum current in tenths of a percent of the set rated current. 3219h:01hI²t Duration Of Max Current - specifies the maximum duration of the maximum current in ms.
Activation Closed loop must be activated. To activate the mode, you must describe the three object entries mentioned above in a meaningful way. This means that the maximum current must be greater than the rated current and a time value for the maximum duration of the maximum current must be entered. If these conditions are not met, the I2t functionality remains deactivated.
Function of I2t From the specification of rated current, maximum current and maximum duration of the maximum current, an I2tLim is calculated. The motor can run with maximum current until the calculated I2tLim is reached. The current is then immediately reduced to the rated current. The maximum current is limited by the maximum motor current (6073h). The relationships are illustrated again in the following diagrams. In the first section, t1, the current value is higher than the rated current. At time t1Lim, I2tLim is reached and the current is limited to the rated current. A current that corresponds to the maximum current then occurs for a period of time t2. Hence, the value for I2tLim is reached more quickly than in time t1.